O-10 Control Word Profile
Select the interpretation of the control and status words corresponding to the installed network. Only the selections valid for the network installed in slot A will
be visible in the Keypad display.
For guidelines in selection of GE Drive profile [0] please refer to the Serial communication via RS 485 Interface section.
Option: Function:
[0] * Drive Profile
O-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0] No function
[1] * Profile Default Function corresponds to the profile default selected in par. O-10 Control Word Profile.
[2] Alarm 68 Only Only set in case of an Alarm 68.
[3] Trip excl Alarm 68 Set in case of a trip, except if the trip is executed by an Alarm 68.
[16] T37 DI status The bit indicates the status of terminal 37.
“1” indicates T37 is high (normal)
only available in AF-650 GP.
O-14 Configurable Control Word CTW
Option: Function:
Selection of control word bit 10 if it is active low or active high
[0] None
[1] * Profile default
[2] CTW Valid, active low
O-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the network.
[0] Digit Input Activates command via a digital input.
[1] Bus Activates command via the serial communication port or network option module.
[2] Logic AND Activates command via the network/serial communication port, AND additionally via one of the digital
inputs.
[3] * Logic OR Activates command via the network/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
O-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the network.
Option: Function:
[0] Digital Input
[1] Bus
[2] Logic AND
[3] * Logic OR
NB!
This parameter is active only when par. O-01 Control Site is set to [0] Digital and control word.
Modbus TCP
35
6